Description
FN SDFs come with the following safety features as a standard offering:
-Terminal Shrouds on both line and load side
-Phase barriers
-High clearances and creepage distances
-High ground clearance
Offering:
-Range: 32A to 800A
-Available in open execution and SS enclosure variants
-Versions: Suitable for DIN type and Bolted type fuses
-HE SDF version for harsh sulphurous environment
-Configurations: 2P, TPN, 4P(100% rated, Switched neutral)
Salient Features:
-AC-23A utilization category for entire range
-Quick-make /Quick-break mechanism
-Quad break contact system : Better arc quenching and higher electrical life of contacts
-Telescopic Shaft: Step-less depth adjustment
-Suitable for Aluminum termination
-Ample space for termination in spacious SS enclosure version
-No separate cable gland boxes required Clear ON/OFF indications
-Door interlocking in ON position with defeat feature
-
Rated Operational Current (A)800A
-
Conformance to StandardsIS/IEC 60947-3, EN 60947-3
-
Fuse TypeDIN /Knife-edge
-
Utilization CategoryAC-23A
-
Rated operational voltage (Ue)415V
-
Operating Frequency(Hz)50/60
-
Mechanical Life (No. of operating cycles)10000
-
Rated Insulation Voltage Ui (V)690V
-
Rated Breaking Capacity@AC-23A (A)6400
-
Rated Making Capacity@AC-23A (A)8000
-
VersionOpen Execution
-
No. of Poles4P
-
Maximum Al termination (sq.mm)2 X 625
-
Mounting positionsAll Orientations
-
Standard AccessoriesTerminal Shrouds, Phase Barriers, Extended handle with shaft
-
Pollution Degree3
-
Discount PercentageBetween 0-10 %