Ambient temperature -20 to 55 degree C 
- 
Mechanical Life (No. of operating cycles) 3600 Cy/Hr 
- 
Rated impulse withstand voltage (Uimp) 8kV 
- 
Rated Insulation Voltage Ui (V) 1000V 
- 
Conformance to Standards IS/IEC 6094741, IEC 6094741 
- 
Coil Voltage 415 V AC 
- 
Rated operational current at 415V 250A 
- 
Discount Percentage Between 0-10 % 
- 
No. of Poles 3P 
- 
Height(mm) 208.2 
- 
Width(mm) 147 
- 
Depth(mm) 181 
- 
Rated kW 132kW 
- 
Rated making capacity 3000A 
- 
Coil Operating band %Uc (Pick up) 80 – 110 % 
- 
Rated breaking capacity 2500A 
- 
Mechanical Life 10 Million 
- 
Coil Operating band %Uc (Drop off) 35 – 65 % 
- 
Pick up VA consumption 960VA 
- 
Hold on VA consumption 56VA